Technical Center
Cable Materials
Conductor, insulation, sheathing and halogen-free compounds.
Material choice sets the temperature rating, the flexibility, the chemical resistance and the fire behaviour of a cable, and it usually sets the price more than the conductor cross-section does. Cross-linked polyethylene allows a higher continuous conductor temperature than PVC and lower dielectric loss, which is why it displaced PVC on power cables above the lowest voltages; ethylene propylene rubber tolerates more repeated flexing and is preferred where a cable must move.
Halogen-free and low-smoke compounds exist because burning PVC releases hydrogen chloride, which is corrosive to equipment and hazardous in a confined space. Halogen-free formulations trade some mechanical toughness and cost for low smoke emission and the absence of acid gas, which is why the requirement usually comes from the installation — tunnels, metro, data halls, offshore — rather than from the cable.
Articles
Standards referenced
- IEC 60502-1 — Power cables with extruded insulation and their accessories for rated voltages of 1 kV (Um = 1.2 kV) and 3 kV (Um = 3.6 kV) — Part 1
- IEC 60332 — Tests on electric and optical fibre cables under fire conditions
- IEC 60754 — Test on gases evolved during combustion of materials from cables
- IEC 61034 — Measurement of smoke density of cables burning under defined conditions