Material choice sets the temperature rating, the flexibility, the chemical resistance and the fire behaviour of a cable, and it usually sets the price more than the conductor cross-section does. Cross-linked polyethylene allows a higher continuous conductor temperature than PVC and lower dielectric loss, which is why it displaced PVC on power cables above the lowest voltages; ethylene propylene rubber tolerates more repeated flexing and is preferred where a cable must move.

Halogen-free and low-smoke compounds exist because burning PVC releases hydrogen chloride, which is corrosive to equipment and hazardous in a confined space. Halogen-free formulations trade some mechanical toughness and cost for low smoke emission and the absence of acid gas, which is why the requirement usually comes from the installation — tunnels, metro, data halls, offshore — rather than from the cable.

Articles

Standards referenced

  • IEC 60502-1 — Power cables with extruded insulation and their accessories for rated voltages of 1 kV (Um = 1.2 kV) and 3 kV (Um = 3.6 kV) — Part 1
  • IEC 60332 — Tests on electric and optical fibre cables under fire conditions
  • IEC 60754 — Test on gases evolved during combustion of materials from cables
  • IEC 61034 — Measurement of smoke density of cables burning under defined conditions